The Crowcon Detective+ is a rugged, water and impact-resistant multi-gas monitor for temporary areas. Ideal for use in turnaround/shutdown procedures, hot work maintenance, confined space entry work, and many other utility, construction, and oil and gas industry applications.
Go solo or link together using Detective Net or cables to form a perimeter, Detective+ gives a loud and clear alarm providing effective warning of gas hazards. The rugged, water and impact-resistant design make Detective+ the ideal choice for your transportable gas detection needs. Methane, Propane, Butane, or Ethylene options.
Infrared sensors
Infrared (IR) sensors for flammable gas can be supplied as a single range, 0-100% LEL, utlising a single display channel, or as a dual range, 0-100% LEL/0-100% volume, which then occupies two display channels. Carbon dioxide sensors are supplied as 0-5% volume. Only one IR sensor can be fitted, and IR sensors can only be used in combination with oxygen and toxic sensors.
Product Range
- Crowcon C2H4DPDRIR Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Ethylene IR
- Crowcon C3H8DPDRIR Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Propane IR
- Crowcon C3H8TRPDRIR Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Propane IR
- Crowcon C4H10DPDRIR Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Butane IR
- Crowcon CH4DPDRIRATEX Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Methane IR ATEX
- Crowcon CH4DPDRIRUL Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Methane IR UL
- Crowcon CH4TRPDRIRATEX Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Methane IR ATEX
- Crowcon CH4TRPDRIRUL Detective Plus IR Sensor Modules - Dual Range 0-100% LEL and 0-100% vol. Methane IR UL
Gas | Range | Typical Alarms |
---|---|---|
Flammable Gas | 0-100 LEL | 20% LEL |
Flammable Gas | 0-100% v/v | None |
Available for methane, propane, butane, or ethylene | ||
Carbon dioxide (CO2) | 0 to 5% v/v | 0.5 and 1.5% v/v |
Specifications | |
---|---|
Size | 640 x 455 x 455mm (25.2 x 17.9 x 17.9ins) |
Weight | 7.5kg (19lbs) |
Alarms | Three large, top-mounted red LED clusters and a single red LED on the front panel Alarm mode: LED clusters flash in quick succession. LED clusters of linked Detectives repeating the alarm, flash slower than LED lights on those Detectives sensing the hazard Normal working: Slow flashing green LED Battery low: Rapid flashing green LED Wailing alarm, omni-direction siren, 104 dBA at 1m |
Display | High contrast LCD with backlight. Values and units for up to 4 gases displayed simultaneously at current, TWA, or peak levels, low battery, real-time and elapsed time calibration, and configuration data also displayed |
Data Logging | 125hrs at 10-second intervals (45,000 logs) |
Event Logging | Alarm, over range, calibration, bump, on/off, TWA, 1000 events |
Battery | Standard 6V, 7.2Ah, sealed lead acid battery pack Optional 6V, 12Ah high capacity pack Up to 36 hours with flammable/ CO2 sensor fitted with 7.2Ah battery Up to 60 hours with an optional 12Ah battery pack |
Typical Response Times | Methane 20s, oxygen 10s, typical toxic gas 20s, IR 20s |
Operating Temperature | -20°C to +50°C (-4°F to 122°F)* |
Expected sensor life | Flammable 5 years, toxic 3 years (typical), oxygen 2 years minimum, IR>5 years |
Humidity | 15-95% RH non-condensing |
EMC | Directive 2014/30/EU EN50270 |
Ingress Protection | IP65 |
Approvals | Europe: ATEX II 2G Ex ib d IIC T4 (Tamb -20°C to +50°C) International: IECEx Ex ib d IIC T4 (Tamb -20°C to +50°C) |
Standards | EN50014, EN50018, EN50020, EN50104, EN45544, IEC60079-0/-1 IEC60079-11 |
PC Interface | Via RS232 lead. Portables PC software can be used to set alarms, clock, data logging interval and password, manage data logging to give a graphical display of instrument log file and allows export to spreadsheet |
Calibration | Quick calibration using the internal menu command, Portables PC |
Sampling | Internal electric sampling pump option, manual aspiration |
Linked Detectives | With cable connection, up to 12 units can be linked to provide perimeter or area monitoring |
Crowcon Connect Compatible? | No |
*Toxic and Oxygen sensors RH Specifications vary, consult Crowcon for specific operating humidities. |
Gases and Ranges Required ranges and alarms may vary by country and application and these can be configured as required. |
||
---|---|---|
Gas | Range | Typical Alarms |
Flammable Gas | 0-100 LEL | 20% LEL |
Oxygen (O2) | 0-25% | 19% & 23% |
Hydrogen Sulphide (H2S) | 0-50 ppm | 10 ppm |
Carbon Monoxide (CO) | 0-500 ppm | 30 ppm |
Sulphur Dioxide (SO2) | 0-10 ppm | 2 ppm |
Chlorine (Cl2) | 0-5 ppm | 0.5 ppm |
Nitrogen Dioxide (NO2) | 0-10 ppm | 2 ppm |
Phosphine (PH3) | 0-5 ppm | 0.5 ppm |
Ammonia (NH3) | 0-50 ppm | 25 ppm |
Ammonia (NH3) | 0-1000 ppm | n/a |
Hydrogen (non-flammable levels) | 0-2000 ppm | n/a |
Hydrogen Cyanide (HCN) | 0-25ppm | 10ppm |
Hydrogen Chloride (HCl)*/+ | 0-10 ppm | 5ppm |
Chlorine Dioxide (ClO2)+ | 0-1 ppm | 0.1 ppm |
Hydrogen Fluoride (HF)+ | 0-10 ppm | 1 ppm |
Ethylene Oxide (C2H4O)* | 0-10 ppm | 5 ppm |
Volatile organic*/+ | 1-100 ppm | n/a |
* One biased sensor per Detective+ + Reactive gas, care required during sampling, contact Crowcon for details. |