An upgraded version of Chauvin Arnoux's CA6416 earth clamp, the CA6417 comes with all of the functionality of the 6416 plus Bluetooth communication and the ability to interface with a PC.
Purpose-built for quick and easy ground loop measurements, the CA6417 is able to simultaneously display the impedance and leakage current of a connected conductor, the ground voltage and the breakdown of resistive and inductive parts of ground impedance.
With 35mm jaws, the clamp meter can easily be used on larger conductors. It also comes with a rotary dial switch for testing type, protective guard, OLED display, backlight and Chauvin Arnoux's unique force compensation system that makes it easier to open the jaws.
Chauvin Arnoux CA6417 Earth Clamp Key Features
- Display of the ground voltage
- Force compensation system
- Automatic Pre-Hold mode
- Automatic calibration of jaw opening
- Possibility of recalibration without returning to the factory
- Programmable alarms on Ω, A and V
- Dangerous Voltage alarm
- Loop resistance measurement from 0.01 to 1,500 Ω
- Ground inductance measurement from 10 to 500 μH
- Leakage current measurement from 0.2 mA to 40 A
- Storage of up to 2,000 time/date-stamped measurements
- GTC and DataView® analysis and report generation software
- Bluetooth connectivity
What's Included?
- Chauvin Arnoux CA6417 Earth Clamp
- Carrying Case
- 4 x 1.5V Batteries
- 1 CD-ROM Operating Manual
- Software
Chauvin Arnoux CA6416/CA6417 Technical Specifications
C.A 6416 | C.A 6417 | |
---|---|---|
Loop Ohmmeter 1500 Count Display | Measurement Ranges (Ω), Resolution (Ω), Accuracy |
|
0.010 to 0.099 / 0.001 / ±1.5 % ±0.01 | ||
0.10 to 0.99 / 0.01 / ±1.5 % ±2 r | ||
1.0 to 49.9 / 0.1 / ±1.5 % ±r | ||
50.0 to 99.5 / 0.5 / ±2 % ±r | ||
100 to 199 / 1 / ±3 % ±r | ||
200 to 395 / 5 / ±5 % ±r | ||
400 to 590 / 10 / ±10 % ±r | ||
600 to 1,150 / 50 / Approx. 20 % | ||
1,200 to 1,500 / 50 / Approx. 25 % | ||
Frequencies | Measurement frequency 2083Hz / transposition frequency 50, 60, 128 or 2083Hz | |
Loop | Measurement Ranges (μH), Resolution (μH), Accuracy |
|
10 to 100/1/±5% ±r | ||
100 to 500/1/±3% ±r | ||
Ground Voltage | Measurements (V) / Resolution (V) | |
0.1 to 4.9/0.1 | ||
5.0 to 49.5/0.5 | ||
50.0 to 75.0/1 | ||
Ammeter (4000-Count Display) | Measurement Ranges (A), Resolution (A), Accuracy | |
0.200 to 0.999 mA / 1 μA / ±2 % ±50 μA | ||
1.000 to 2.990 mA - 3.00 to 9.99 mA / 10 μA / ±2 % ±50 μA | ||
10.00 to 29.90 mA - 30.0 to 99.9 mA / 100 μA / ±2 % ±r | ||
100.0 to 299.0 mA - 0.300 to 0.990 A / 1 mA / ±2 % ±r | ||
1.000 to 2.990 A - 3.00 to 39.99 A / 10 mA / ±2 % ±r | ||
Setup | ||
Modes | Standard or Advanced | |
Alarms | Configurable on Z, V and A | |
Buzzer | Active | |
HOLD | Manual or automatic PRE-HOLD | |
Automatic Power-Off | Active/Inactive | |
General Specifications | ||
Display | 152-segment OLED. Active area 48 x 39 mm | |
Max. Clamping Diameter | Ø 35 mm | |
Storage | 300 time/date-stamped measurements | 2,000 time/date-stamped measurements |
Communication | - | Bluetooth Class 2 |
Power Supply | 4 x 1.5V LR6 (AA) alkaline batteries or 4 x NiMH batteries | |
Battery Life | 1440 measurements of 30 seconds each | |
Calibration | Automatic at start-up | |
Electrical Safety | IEC 61010 600V CAT IV | |
Protection | IP40 | |
Dimensions | 55 x 95 x 262mm | |
Weight | Approx 935g with batteries |
Reviews
SKU | P01122016 |
---|---|
Manufacturer Part Code | P01122016 |
Country of Origin | France |