The Chauvin Arnoux CA 6163 is delivered in a yellow site case. It is equipped with a colour touch screen usable even when wearing gloves. Its user interface is multilingual and there are numerous help screens available at all times during use. In this way, users are guided by visuals, text, and symbols. The CA 6163 can store up to 100,000 tests in its memory. It communicates via Wifi or its USB ports. PC software transfers the data from completed tests via USB or Wifi for analysis and report generation. Firmware upgrades are performed very simply using a USB drive.
The CA 6163 machine tester is equipped with a keypad with four keys for quick access to certain functions whatever the context may be: printout of a measurement on the sticker/label printer, display of helps screens for the selected function, return to the home screen and return to the previous screen. In particular, this can be used to return quickly to the home screen, wherever you are in the HMI tree structure. The CA 6163 is equipped with interfaces for a barcode reader, RFID reader, remote control, and lamps. Thanks to its numerous accessories, it can also be used to print our Pass/Fail stickers automatically.
The CA 6163 is ideal for the inspection and certification of appliances' electrical safety in the context of:
It will be used frequently by:
CA 6163 Specifications | ||
---|---|---|
High Voltage | High Voltage | 40 - 5,350 V |
Resolution / Accuracy | 10 V / ±(1% R + 2 cts) | |
Max. Current | 200 mA | |
I Measurement Ranges | 100 mA / 200 mA | |
Resolution / Accuracy | 0.1 mA - 1 mA / ±(2% R + 2 cts) | |
Insulation | Test Voltage | 100 V / 250 V / 500 V / 1,000 V |
Max. Measurement | 50 GΩ* | |
Range | 9.999 MΩ / 99.99 MΩ / 999.9 MΩ / 50.00GΩ | |
Resolution / Accuracy | 1 kΩ - 10 kΩ - 100 kΩ/ ±(2% R + 2 cts) 10 MΩ / ±(10% R + 2 cts) |
|
Continuity | Measurement Current | 25 A* |
Measurement Range | 0.005-0.400 Ω | |
Resolution | 0,001 Ω | |
Accuracy | ±(2% R + 2 cts) | |
Timer Max | 03 min: 00s | |
Leakage Current | I-PE-direct & I-differential Range / Resolution / accuracy |
Test socket: 30.00 mA / 0.01 mA / ±(2% R + 2 cts) ; polarity reversal Clamp: 1 A-10 A-40 A / 0.1 mA-1 mA-10 mA / ±(2.5% R + 2 cts) |
I-substitution | Test socket: 50.00 mA / 0.01 mA / ±(2% R + 2 cts) | |
Touch Leakage | Socket and “tripod”: 30.00 mA / 0.01 mA | |
Measurement network | Unweighted, weighted, L-N polarity reversal, welding machine | |
Loop/Integrated Fuse Table Zs without trip (Zs & Rs) |
Range / Resolution | 2 Ω; 40 Ω; 400 Ω; 2,000 Ω / 0.01Ω; 0.01Ω; 0.1Ω; 1Ω |
Accuracy | ±(15% R + 3 cts) ; ±(10% R + 3 cts) ; ±(5% R + 2 cts) ; ±(5% R + 2 cts) | |
Ik Display Range | 12 kA | |
Loop/Integrated Fuse Table ZS high current and Zi |
Range / Resolution | 0.5 Ω; 3.999 Ω; 39.99 Ω; 400.0 Ω / 0.001Ω; 0.001Ω; 0.01Ω; 0.1Ω |
Accuracy | ±(10% R + 20 cts); ±(10% R + 20 cts) ; ±(5% R + 2 cts) ; ±(5% R + 2 cts) | |
Ik Display Range | 20 kA | |
Loop/Integrated Fuse Table Inductance |
Range / Resolution / Accuracy | 15.0 mH / 0.1 mH / ±(10% R + 2 cts) |
Loop/Integrated Fuse Table UF Measurement |
Range / Resolution / Accuracy | 24.9 V; 70.0 V / 0.1 V; 0.1 V / ±(15% R + 3 cts) / ±(5% R + 2 cts) |
RCD & PRCD | Network Voltage | 440 VAC max |
Calibres | 10 / 30 / 100 / 300 / 500 / 1,000 mA / Var (6 - 1,000 mA) | |
Types of RCD | AC, A, F, B, B+; G, S | |
Pulse test | x 0.5; x 1; x 2, x 4; x 5; x 10 (DC) I∆n | |
Tripping Time - Range / Resolution / Accuracy | 300 ms / 0.1 ms / ±2ms | |
Ramp Test | 10 / 30 / 100 / 300 / 500 / 1,000 mA, Var (6-1,000mA); 0.3 x I Δn to I test max / 22 steps | |
Tripping Current - Resolution / Accuracy | 0.1 mA; -0% +(7%R + 2 mA) | |
UF Measurement Range / Resolution / Accuracy | 24.9 V; 70.0 V/ 0.1 V / ±(15% R + 3 cts) ; ±(5% R + 2 cts) | |
Discharge Time 34 V, 60 V, 120 V | Time | 0.1 s - 9.9 s / 0.1 s / ±(1% R + 1 ct) |
Up Voltage Range / Resolution / Accuracy | 207.0-375.0 / 0.1 V / ±(2% R + 2 cts) & “Tripod”: 1-650 V / 0.1 V / ±(2% R + 2 cts) | |
Test Socket Power Values | Quantities | Socket: U, I, P, S, F, cos ϕ, Pf, THD U, THD I |
Measurement Range | 265 VAC ; 16 A; 4.24 kW; 4.24 kVA; 45-55 Hz;(-1,+1); (-1,+1); 8.0 %; 100 % | |
Range / Resolution / Accuracy | 100 W; 1 kW; 4.24 kW / 0.01 W; 0.1 W; 1 W / ±(2% R + 2 cts) | |
Phase Rotation | Installation Voltage and Frequency | 190.0 - 440.0 V; 45-55 Hz |
General Specifications | Display | Colour touch screen; TN 800 x 480, 5" |
Data Storage | 100,000 tests | |
Timer Max. | 40 min (depending on the type of test) | |
Communication | 1 x USB-B; 2 x USB-A, Wifi | |
Interfaces | START/STOP pedals, DOOR Open, HV gun trigger, 4 lamps, Barcode reader, RFID reader, sticker printer | |
Power Supply | 230 VAC ±10%; 220 VAC -6% + 15 % | |
Dimensions / Weight | 407 x 341 x 205 mm; 16 kg | |
Temperature | OPERATION: 0; + 45 °C ; STORAGE: - 30; + 60 °C | |
Protection | IP 40 open / IP 64 closed; IK 08 | |
Electrical Safety | IEC 61010-1; IEC 61010-2-030; IEC 61010-2-034; 300 V CAT II; 300V CAT III; 600V CAT III | |
Standards | IEC 61557-1; -2; -3; -4; -6; -7; -10; -13;-14; -16 (partial) |
*except with test socket