The Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester can be used to test for voltages between 12 and 690V AC/DC. Readings are indicated via the LED display along with the voltage polarity. When readings above 50V AC or 120V DC are detected the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester will issue an audible alert.
The Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester will also issue an audible and visual alert when a voltage is detected during single-phase voltage detection tests (conducted using the main probe) and will indicate the presence of continuity via the illumination of a dedicated LED. Continuity tests are conducted automatically.
In addition to this, the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester features two pole phase rotation indication (right) and can conduct single pole tests to verify phase polarity.
Further to this, the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester is suitable for checking that 10mA and 30mA RCDs are wired correctly. These components can be tripped remotely by pressing both of the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester’s buttons. When both of these buttons are pressed the unit is placed in low-impedance mode, thereby preventing ghost voltages from affecting the accuracy of the readings.
However; when neither of the buttons is pressed the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester is in high-impedance mode which prevents the accidental tripping of RCDs and ELCBs. Moreover, this mode improves the safety of the instrument when checking live power sources.
Also adding to the safety of this instrument is its rugged, IP64 design. It is resistant to dust and water ingress and is equipped with a 1.5m, wear-indication test lead. Furthermore, the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester is constructed according to the standard EN 61243-3:2010, has a safety rating of CAT IV 600V/ CAT III 690V and is GS approved. It is supplied with GS38 protective probe caps and these caps, as well as the 4mm test probe extensions, can be stored in the conveniently designed test probe protector cover. The protector cover is connected to the tester and features a tip that can be used to open UK electrical safety outlets.
This robust, durable and practical design makes the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester suitable for use in industrial and commercial environments. It also features a torch for illuminating the measurement area, ensuring that the tester can be used in dark or dim locations.
Finally, it features Auto Power ON/OFF and OFF buttons which work to preserve the battery life of the Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester, as well as improve the ease with which this instrument can be operated.
The Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester is the entry model in Amprobe’s series of 2100 Two Pole Voltage Testers; nevertheless, it is a comprehensive, durable and easy-to-use instrument suitable for a multitude of applications within commercial and industrial environments.
Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester Key Features
- Test for voltages between 12 and 690V AC/DC
- Readings are indicated via the LED display
- Automatically indicates voltage polarity
- Issues an audible alert when voltages above 50V AC or 120V DC are detected
- Issues an audible and visual alert when a voltage is detected during single-phase voltage detection tests
- Single-phase voltage detection tests are conducted using the main probe
- Automatic continuity test
- The presence of continuity is indicated via an LED
- Two pole phase rotation indication (right)
- Suitable for checking that 10mA and 30mA RCDs are wired correctly
- Pressing the two buttons allows 10mA or 30mA RCDs to be tripped remotely
- Pressing both buttons puts the tester in low-impedance mode
- Low-impedance mode eliminates the effects of ghost voltages
- When neither of the buttons is pressed the tester is in high-impedance mode
- High-impedance mode prevents the accidental tripping of RCDs and ELCBs
- The high-impedance mode also improves the safety of the instrument when checking live power sources
- Rugged, IP64 design
- Equipped with a 1.5m, wear-indication test lead
- Constructed according to the standard EN 61243-3:2010
- Safety rating of CAT IV 600V/ CAT III 690V
- GS approved
- Supplied with GS38 protective probe caps
- Caps and 4mm test probe extensions can be stored in the test probe protector cover
- Test probe protector cover features a tip optimised for opening UK electrical safety outlets
- Torch
- Auto Power ON/OFF and OFF buttons
- Entry model in Beha-Amprobe’s 2100 series of Two Pole Voltage Testers
- A comprehensive, durable and easy-to-use instrument suitable for a multitude of applications within commercial and industrial environments
What’s Included?
- Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester
- 4mm Test Probe Extensions with GS38 Protective Probe Caps
- Test Probe Protective Cover
- 4-Year Product Warranty from Amprobe
Beha-Amprobe 2100-Alpha Two Pole LED Voltage Tester Technical Specifications
2100-Alpha | 2100-Beta | 2100-Gamma | |
---|---|---|---|
Voltage Test |
|||
LED Voltage Range |
12…690 V AC/DC |
12…690 V AC/DC |
12…≥690 V AC/DC |
LED Indicator |
±12, ±24, 50, 120, 230, 400, 690 V |
±12, ±24, 50, 120, 230, 400, ≥690 V |
|
LED Tolerances |
acc. To EN 61243-3:2010 |
||
LCD Voltage Range |
- |
12…690 V AC/DC |
6…1000 V AC/ 6…1200 V DC |
LCD Resolution |
- |
1 V |
|
LCD Tolerance |
- |
± (3% rdg + 3 LSD) |
|
LED and LCD Response Time |
< 1s |
||
Frequency Range |
DC, 16 2/3 Hz…400 Hz |
||
Acoustic Indication |
≥ 50 V AC, ≥ 120 V DC |
||
Voltage Detection |
Automatic (AC/DC) |
||
Polarity Detection |
Full Range |
||
Range Detection |
Automatic |
||
Current I (load buttons not activated) |
≤3.5 mA AC/DC at 690 V AC/DC |
≤3.5 mAAC at 1000 VAC/ 4.5 mADC at 1200 VDC |
|
Internal Load (load buttons not activated) |
Approximately 2.4 W at 690 V AC/DC |
Approximately 3.5 W at 1000 VAC / Approximately 5.4 W at 1200 VDC |
|
Test Current Switchable Load (load buttons activated) |
≤350 mA AC/DC at 690 V AC/DC |
≤300 mAAC at 1000 VAC / ≤350 mADC at 1200 VDC |
|
Switchable Load (load buttons activated) |
Approximately 240 W at 690 V AC/DC |
Approximately 300 W at 1000 VAC / Approximately 420 W at 1200 VDC |
|
Automatic Power ON |
LED: >12 V (activated load buttons) >24 V (w/o load buttons) |
LED: >12 V (activated load buttons) >24 V (w/o load buttons) LCD: >12V |
LED: >12 V LCD: > 6V |
Trip Test RCD (earth leakage circuit breaker) |
|||
Test Current Switchable Load (load buttons activated) |
>30 mAAC at 230 VAC |
||
Single Pole Phase Test |
|||
Voltage Range |
180…690 VAC against earth |
100…1000 VAC against earth |
|
Frequency Range |
40Hz… 70Hz |
||
Acoustic Indication |
Yes |
||
Indication |
Red LED |
||
Continuity Test (Rx)/ Diode Test |
|||
Range |
0….500 kΩ |
||
Tolerance |
0% to +50% |
||
Test Current |
<5 μA |
||
Acoustic Indication |
Yes |
||
Diode Test |
Yes |
||
Indication |
RED LED |
||
Overvoltage Protection |
690 V AC/DC |
1000 VAC/ 1200 VDC |
|
Automatic Power ON |
< 500 kΩ |
||
Phase Rotation Indication |
|||
Voltage Range |
340…440 V AC phase to phase |
170…1000 V AC phase to phase |
|
Frequency Range |
47…63 Hz |
40…70 Hz |
|
Indication |
Red LED |
||
Resistance Measurement (Ω)/ Low Resistance Indication (2100-Gamma only) |
|||
Resistance Range on LCD |
0….1999 Ω |
||
Resolution |
1 Ω |
||
Tolerance |
± (5% rdg + 10 LSD) at 20°C |
||
Temperature Coefficient |
± (5 LSD / 10 K) |
||
Test Current |
<30 μA |
||
Low Resistance Indication |
Acoustic Indication <10…50Ω |
||
Overvoltage Protection |
690 V AC/DC |
1000 VAC/ 1200 VDC |
|
Non-Contact Voltage Indication/ Electric Field (NCV/EF) |
|||
Voltage Range |
- |
100…1000 VAC |
|
Frequency Range |
- |
50…60 Hz |
|
Indication |
_ |
3 levels shown by LCD segments |
|
Data Hold |
|||
Data Hold |
_ |
Only voltage measurements (12…690V AC/DC) |
Voltage and resistance measurements, NCV |
Measurement Illumination Area/ Torch Light |
|||
Torch Light |
White LED |
||
General Specifications |
|||
Operation Time (DT) |
30s |
||
Recovery Time |
240s |
||
Operating Temperature |
-15°C to +55°C |
||
Storage Temperature |
-15°C to +55°C |
||
Humidity |
Max. 95% RH |
||
Operating Altitude |
Up to 2000m |
||
Safety Rating (Overall Voltage Category) |
CAT IV / 600V, CAT III / 690V |
CAT IV / 600V, CAT III / 1000V |
|
Pollution Degree |
2 |
||
Protection Degree |
IP64 |
||
Safety Regulations |
IEC 61243-3:2009, EN 61243-3:2010, DIN VDE 0682-401:2011 |
||
Approvals, Compliance |
GS mark from TÜV Rheinland, CE |
||
Power Supply |
Battery 2 x 1.5V (AAA/ IEC LR03) |
||
Power Consumption |
Approximately 60mA |
||
Battery Lifetime |
More than 10000 measurements (<5 s/ per measurement) |
||
Dimensions (HxWxD) |
Approximately 280 x 78 x 35 mm (11.0 x 3.1 x 1.4 in) |
||
Weight |
Approximately 320 g (0.71 lb) |
Reviews
SKU | 4312495 |
---|---|
Manufacturer Part Code | 4312495 |
Country of Origin | China |