FREE - PASS The Complete Guide to EET (PAT) Testing, 5th Edition
Buy a PAT testing kit and get an updated PAT Testing Guide worth £24.99. This 129 page indepth PAT testing book is a great addition to your kit. View PAT Guide
Fluke 6200-2 PAT Tester - Kit 2
Our best bundle option available with the Fluke 6200, this kit contains essential PAT testing accessories such as labels and adaptors for testing specialist devices such as IT equipment and also comes with a software package that allows comprehensive record keeping of PAT testing results.
The Fluke 6200 is a manual based PAT tester that can be used absolutely anywhere from in an office to testing appliance in an industrial environment. The device is simple-to-use, is designed to speed up the time spent testing thanks to a number of built-in testing procedures and includes all of the necessary testing procedures to effectively test class I and class II appliances as well as IEC leads and extension leads.
Measurement functions available on this device are L N mains volts, outside limit indicators, protective earth resistance (200mA and 25A), insulation at 500V DC, protective earth conductor current, touch current, substitute leakage current, appliance power kVa, appliance load current, IEC lead testing and checks of polarity.
Tests are designed to be initiated with minimal fuss, often requiring only a simple button press to get started. It is also possible for the user to directly configure the test, allowing adjustments to be made for different types of appliance.
The 6200 is lightweight, includes a large-size backlit LCD screen and also comes with a carrying handle to make porting it from test to test quick and easy.
Key Features
- Dedicated key for each test for one touch testing
- Pre-set pass/fail levels to save time
- Large backlit display for easy reading
- Single mains socket for appliance connections
- IEC socket
- Detachable test leads
- Integral carrying handle
- Lightweight design
- Large size backlit screen
- Earth resistance testing
- Insulation testing
- Current testing
- Polarity checks
- Test IEC leads
Fluke 6200 - Bundle 2 Accessories
You won't get this deal anywhere else - our PAT testing bundles are designed to be as low in price as possible and contain a huge amount of essential items you'll be able to use every day when out PAT testing.
Bundle 2 is our best bundle option available for the Fluke 6200, including everything you receive in Bundle 1 as well as a software package that allows you to enter data from your 6200 manually in order to create comprehensive records of your PAT testing.
This kit contains:
- Fluke 6200-2 PAT Tester
- User Manual on CD-ROM
- Quick Reference Guide
- Soft shell Carrying Case
- Test Lead
- Test Probe
- Crocodile Clip
- Mains Cord
- Socket Tester
- eLearning PAT Testing Course - Includes Exam and Certificate
- PASS PAT Testing Logbook
- Microwave Leakage Detector
- PASSPTA21 - IEC to Cloverleaf Adapter
- PASSPTA29 - IEC Plug to Cloverleaf Adapter
- PASSPTA28 - IEC Plug to Fig 8 PAT Adapter
- CK Tools 5 Piece Insulated Screwdriver Set
- 500 x Passed PAT Testing Labels
- 500 x Circular Passed PAT Testing Labels
- 250 x Cable Wrap PAT Labels
- 250 x Failed PAT Labels
- SimplyPATs Manual Entry Software
Our Fluke 6200-2 PAT Bundles
Why not also consider upgrading to Bundle 2 instead?
Item Description | Fluke 6200-2 PAT Tester Essentials Kit (Bundle 1) | Fluke 6200-2 PAT Tester Professional Kit (Bundle 2) |
---|---|---|
Soft Shell Carrying Case Keep all of your equipment safe and in one place with this large-size carrying case with a customisable foam insert (The appearance of the case may vary depending on current stock) |
√ | √ |
Socket Tester Need to check if your sockets are working right? Just plug this in to a standard UK plug socket and if there's a problem, the socket tester will let you know about it! |
√ | √ |
eLearning PAT Testing Course - Includes Exam and Certificate Gain a certificate of competency to carry out PAT testing in just two hours with our online PAT course and exam. Teams of staff may be trained by purchasing the course multiple times; each staff member will be assigned a unique activation code and login. |
√ |
√ |
PASS PAT Testing Logbook Keep a record of all of your testing with our logbook. The book includes carbon-copied records, allowing you to keep one for yourself and give the other to customers or keep for a reference. |
√ | √ |
Microwave Leakage Detector When PAT testing, it's common practice to check microwaves are also not emitting high levels of radiation. With our microwave leakage detector you'll be able to do this testing with ease. |
√ | √ |
PASSPTA21 - IEC (C13 Female) You'll need this adaptor to connect your PAT tester to laptop/PC power leads and other similar equipment which has a cloverleaf-shaped connector. |
√ | √ |
PASSPTA29 - IEC Plug (C14) This adaptor is used to connect to laptop power supplies, portable projectors and other similar equipment. |
√ | √ |
PASSPTA28 - IEC Plug (C14) You'll find several appliances such as game consoles, laptop power supplies, audio/visual equipment and more use this type of connector - with this adaptor, you can connect them up to your PAT tester. |
√ | √ |
CK Tools AV05050 5 Piece Insulated Screwdriver Kit A handy set of insulated screwdrivers (suitable for live working to 1000V) suitable for a wide variety of applications. |
√ | √ |
WM1 - 500 x Passed PAT Testing Labels You'll need these every time an appliance passes a test - just tear one off, fill in the fields (appliance ID, your name, test date and next test due date) and stick on the appliance when done. |
√ | √ |
WM6500 - 500 x Circular Passed PAT Testing Labels These circular-shaped PAT labels are great for plug tops and any other appliance. The labels also include space for ticking the month/year the next test is due. |
√ | √ |
WM12 250 - 250 x Cable Wrap Labels These passed labels wrap around a wire/cable from an appliance and are recommended for use with power supplies or on appliances where you can't stick a label. They also include space for writing your appliance ID, name, test date and next test date. |
√ | √ |
WM7 250 - 250 x Failed PAT Testing Labels You won't need these as often as your passed labels, but you'll need to apply one of these whenever an appliance fails a test. If it does fail, the item should be taken out of service for repair or replacement |
√ | √ |
SimplyPats Manual PAT Testing Software Keep a database of your PAT testing information on your PC and print reports with SimplyPats Manual software. Please note that this software is manual entry; you cannot download directly from the PAT tester and you will need to type in records by hand. |
- | √ |
- PASS The Complete Guide to EET (PAT) Testing, 5th Edition - PASS-PAT-HB, typically £24.99
Fluke 6200 Technical Specifications
General Specs | |
Size | 200m (L) x 275mm (W) x 100mm (H) |
Weight | 3kg |
Power Supply | 230V + 10% - 15%, 50Hz ±2% |
Power Consumption | 13W Typical (Idle) 60W Max, during 25A Bond Test |
Operating Temperature | 0 to 40°C |
Storage Temperature | -10 to 60°C |
Relative Humidity | Non Condensing <10°C 95% from 10 to 30°C 75% from 30 to 40°C |
Operating Altitude | 0 to 2000m |
Sealing | IP-40 (enclosure) IP-20 (connectors) |
EMC | Complies with EN61326-1, Criteria B |
EMI Immunity | 3 V/m |
Safety | Complies with EN61010-1 2nd Edition CAT II, 300V, Pol 2 |
Test Specifications | |
Power On-Test | |
Display Range | 90V to 264V |
Accuracy at 50Hz | ± (2% + 3 counts) |
Resolution | 0.1V (1V - model 6200) |
Input Impedance | > 1MΩ // 2.2nF |
Maximum Input Mains Voltage | 300V |
Earth Bond Test (RPE) | |
Display Range | 0 to 19.99Ω |
Accuracy (after Bond Test Zeroing) | ± (5% + 4 counts) |
Resolution | 0.01Ω |
Test Current | 200mA ac -0 + 40% into 1.99Ω 25A ac ± 20% into 25 mΩ at 230V |
Open Circuit Voltage | >4V ac, <24 Vac |
Bond Test Zeroing | Can subtract up to 1.99Ω |
Insulation Test (Riso) | |
Display Range | 0 to 299MΩ |
Accuracy | ± (5% + 2 counts) from 0.1 to 50MΩ ± (10% + 2 counts) from 50 to 299MΩ |
Resolution | 0.01MΩ (0 to 19.99MΩ 0.1MΩ (20 to 199.9MΩ) 1MΩ (200 to 299MΩ) |
Test Voltage | 500V DC -0% +25% at 500kΩ load |
Test Current | >1mA at 500kΩ load, <15mA at 0Ω |
Auto Discharge Time | <0.5s for 1μF |
Max Capacitive Load |
Operational up to 1μF |
Further technical specifications can be found in the attached datasheet.